Mobile Gasfackel von AB Industrie Service mit großer Flamme im Einsatz

H₂-ready Buy · Hire · Have us flare for you

Mobile gas flares DN 25 & DN 50Flare residual gas safely and prove it

Rugged stainless-steel flaring units for natural gas, biogas, propane, town gas and hydrogen — the DN 50 up to 16 bar. DBI-tested with over 99 % burnout under Article 17 of the EU Methane Regulation. Buy, hire or let us do the flaring.

16 barmax. inlet pressure 2.000 m³/hthroughput DN 50 5gas types · incl. H₂ Venturi nozzleempty down to ppm range up to 100 barpressure reduction station · ATEX
DBI geprüft / tested – Prüfzertifikat DBI Freiberg
Mobile Gasfackel beim Abfackeln an einer Gasstation — AB Industrie Service
H₂ready — hydrogen capable
Gasfackel DN 50 beim Abfackeln im Pipelinebau
16 barmax. inlet pressure
Volumen-Messkoffer zur Dokumentation der abgefackelten Gasmenge
DBItested & documented
Mobile Druckreduzierstation bis 100 bar (ATEX)
100 barPressure-reducing station · ATEX
Edelstahl-Anschluss eines mobilen Abfackelgeräts im Detail
1.4301Stainless, low-maintenance
DBI-testedGas Technology Institute Freiberg, TA-Luft
DVGW-certifiedFlashback arrestors GRS25 & GRS50/GRV50 (IBEDA)
EU Methane Regulation2024/1787 — auditable documentation
Stainless 1.4301low-maintenance, built for outdoors
CE-compliantEN 1762:2018, ISO 3821

EU Methane Regulation 2024/1787

Does your gas flare meet Article 17?

Article 17 of the regulation sets two requirements for gas flares. For all units — including existing ones — the deadline expired on 5 February 2026. The DN 25 and DN 50 gas flares meet both, verified by DBI Freiberg.

01

At least 99 % destruction and removal efficiency

The regulation permits no more than 1 % residual methane in the exhaust. DBI — Gastechnologisches Institut gGmbH Freiberg, an independent group of companies within DVGW — tested both sizes to EU Methane Regulation 2024/1787, VDI 2105 (10/22) and TA-Luft (08/2021). Both units carry the DBI test mark.

02

Auto-igniter or continuous pilot burner

Both gas flares use a standing propane pilot flame that burns throughout the entire flaring operation. That is precisely why the regulation requires it: escaping gas is re-ignited at any time, even if the main flame briefly goes out. A 6 kg propane cylinder typically lasts 48 to 72 hours of continuous operation.

03

And the documentation obligation?

Flared volumes must be recorded and documented in a verifiable manner. The volume measuring case logs flow rate and quantity as a PDF alongside the flaring operation — for authorities, QM and audits.

What DBI measured

DBI test report no. 81-8108-2024 dated 19 Dec 2024. Limit under the EU Methane Regulation: no more than 1 % residual methane in the exhaust.
FeatureHighest measured residual methaneBurnout
Gasfackel DN 250,16 %at least 99.8 %
Gasfackel DN 500,57 %at least 99.4 %

On the DN 25, no residual methane was detectable from 0.5 bar flow pressure upwards. On the DN 50, the highest value was measured at flow rates up to 1,800 m³/h.

And in hydrogen operation? In January 2025 DBI additionally tested the DN 25 with pure hydrogen (99.9 %). At 100 to 360 m³/h and 0.10 to 0.40 bar flow pressure, unburnt residual hydrogen ranged between 13 and 0.5 ppm — DBI certifies complete burnout up to 0.4 bar and 360 m³/h. According to the report, hydrogen operation produces significantly higher NOx values than natural gas; for short-term flaring these are not subject to limit values.

What else Article 17 requires from the operator

The two requirements above concern the unit. Two more are addressed to you as the operator. We reproduce them here to the best of our knowledge — assessing them for your plant is up to you.

Flame monitor with a continuous pilot burner

“Where auto-igniters or continuous pilot burners are used, operators shall use flame monitors for continuous monitoring of the main flame or the pilot flame to ensure that no gas is released unburnt.”Article 17(4)

Our units work with a continuous pilot burner. The optical flame monitoring performs exactly this task — it is included in the PREMIUM PRO PLUS (DN 25) and PREMIUM-PRO+ (DN 50) versions. We recommend it; whether it is required for your application is your decision.

Inspection before every use

“Where the gas flares or other combustion devices are not used regularly, operators shall inspect them before each use.”Article 17(3)

Regularly used flares must be inspected every 15 days. Mobile units are usually deployed irregularly — then the check applies before every use. Any irregularities found must be rectified within six hours. We brief your team on this.

These statements reproduce the text of the regulation and do not constitute legal advice. How Article 17 applies to your plant is for you or your consulting engineer to assess.

Not sure whether your existing unit provides the evidence? Give us a call — we will go through the requirements with you.

Gasfackel am Rand eines Waldwegs, die Flamme steht über den Baumkronen; ein Mitarbeiter in Warnkleidung sichert die Stelle ab.
Gasfackel auf dem Stativ vor einer Gasübergabestation, daneben der geöffnete Transporter mit der Ausrüstung.
Wintereinsatz: Gasfackel im Schnee, daneben eine Leiter und der Transportkoffer.

Product range

Which gas flare suits your pipeline?

Two flare sizes plus matching system components — from house connections to the 100-bar pipeline. All units in stainless steel, multi-gas capable (natural gas, biogas, propane, town gas, hydrogen) and available in several versions.

Gas flares

DN 25 · 1"Mobile Gasfackel DN 25 — Abfackelgerät aus Edelstahl

Gas flare DN 25

The mobile all-rounder for distribution grids and house connections — compact and quick to set up.

  • ~700 m³/hat 5 bar flow pressure
  • 5 mbar – 5 barpressure range
  • GRS25IBEDA · DVGW-certified
  • Stainless 1.4301 · piezo propane igniter
  • 4 versions — ECO (brass) to PREMIUM PRO PLUS with VENKRO 25 venturi nozzle and flame monitoring
View product
Pricefrom €5,499 netEnquire
DN 50 · 2"Mobile Gasfackel DN 50 — Abfackelgerät für den Hochdruckbereich

Gas flare DN 50

For large volumes and high-pressure work — transmission lines, pipeline construction, wells.

  • ~2.000 m³/hat 5 bar flow pressure
  • 5 mbar – 16 barpressure range
  • GRV50IBEDA · DVGW-certified
  • Integrated pre-filter · stainless 1.4301
  • 8 versions — two pressure ratings (5 or 16 bar) times four equipment levels
View product
Pricefrom €11,294 netEnquire

System components

Mandatory logVolumen-Messkoffer für die Dokumentation nach EU-Methanverordnung

Volume metering case

Measures and logs the flared volume — the mandatory companion for auditable documentation under the EU Methane Regulation.

  • 2,5–250 m³/hrange · up to 16 bar
  • ± 1,5 %accuracy · density-independent (Kármán)
  • Wi-Fi remote · SCADA · PDF report
  • Supplied with calibration certificate
View product
Price€10,990 netEnquire
NEW · up to 100 barMobile Druckreduzierstation bis 100 bar für Methan und Wasserstoff

Mobile pressure-reducing station

Reduces pipeline pressures up to 100 bar to a safe flaring pressure — with minimal installation effort. ATEX-certified, for methane and hydrogen.

  • 40–100 barginlet → 10–25 barg outlet
  • 1.800 / 4.800 Nm³/hmethane / hydrogen
  • DN 40 · Kvs 2,5ATEX-certified fittings
  • Piston regulator · pre-filter · glycerine gauge
Priceon requestEnquire

Why the measurement does not depend on the type of gas

A bluff body sits across the pipe. Behind it, vortices detach alternately to the left and right — a regular double row, named after the physicist Theodore von Kármán. Over a wide range, how often a vortex detaches depends solely on the flow velocity: twice the speed, twice the frequency.

Flow

Bluff body

0,3 m/s30 m/s

6,0 m/s·× 20 vortices per second compared with 0.3 m/s

Watch this while dragging: the vortices do not move closer together. Their spacing is set by the width of the bluff body, not by the velocity — they simply pass by faster. That is precisely why more of them reach the sensor per second.

Schematic, not to scale. Behind the bluff body the vortices detach alternately from either side; the two rows rotate in opposite directions and are offset by half a spacing. The shedding frequency f follows f = Sr · v / d from the flow velocity v and the width of the bluff body d — the Strouhal number Sr stays nearly constant over a wide range. Which is exactly why: twice the velocity, twice the frequency.

Put simply

Hold a stick in a stream. Behind it, eddies form — one to the left, the next to the right, always alternating. If the water runs faster, the eddies follow each other faster. That is exactly what happens in the measuring case, only with gas: a bluff body sits in the pipe, and behind it the unit counts the vortices. The number of vortices per second gives the velocity; velocity times pipe cross-section gives the quantity. The same phenomenon makes a flag flutter in the wind and an overhead line sing in a storm.

The slider spans the unit's measuring range: 0.3 to 30 m/s in the measuring section. The figures are to scale. The motion in the picture is compressed — across the whole range the frequency changes a hundredfold, which at the upper end could no longer be followed.

The measuring case counts these detachments. Because only their frequency matters and not the force of the flow, the density of the gas is irrelevant. For flaring that is the decisive point: natural gas, biogas, propane and hydrogen differ in density by a multiple — a density-dependent method would have to be recalibrated for every type of gas.

You specify the gas — the device does not. For the conversion to standard cubic metres you enter into the device which gas you are flaring. It cannot verify this: it counts vortices, not composition. Whatever is entered, it takes as given. The wrong gas means the wrong standard value — and that value then appears in the report for the authorities.

All prices net, plus 19 % VAT · As of 07/2026 · Binding prices for all versions in the shop

You are not just buying a device. We configure it for your application. We service it, repair it and handle the annual inspection of the fittings — in our workshop in Leipzig. On the phone you reach someone who does the flaring himself. And when it is urgent, a hire unit is ready for collection within an hour. Anyone looking only at the purchase price will find cheaper. Anyone who wants the device to work when they are standing in front of it is in the right place.

Key features

What sets our flaring technology apart technically

DN 50 Abfackelgerät mit Verlängerungsrohr für maximalen Fließdruck

Maximum flow pressure

DN 50 up to 16 bar, DN 25 up to 5 bar. Flow pressure is the pressure actually present at the unit while flaring — the higher it is, the greater the possible gas throughput.

Flow pressure = the pressure in the moving gas right at the unit (not the static pressure). It determines how much gas can be safely flared per hour.

On site

Shown: the upper riser with flame monitoring and the fitted diffuser extension tube (DN 50, +1,800 mm, stainless V2A). At high flow pressure the extension pushes the flame outlet further up — heat radiation moves upward and radiant heat at ground level drops noticeably. Guyed with three eyelets, use from 1 bar line pressure.

Venturidüse am Abfackelgerät — leer bis in den ppm-Bereich

Venturi nozzle – empty down to ppm

The venturi nozzle — VENKRO 25 for the DN 25, VENKRO 50 for the DN 50, both patent pending — actively draws the residual gas out of the line, down to the ppm range and thus far below 50 % LEL. A separate nitrogen purge can be dispensed with: no cylinders to order, transport, connect and return.

Venturi nozzle = a constriction where flowing compressed air creates a vacuum and draws residual gas out of the line — without any pump.

On site

Shown: the Venturi nozzle with compressed-air connection. How to draw down the line — oil-free compressed air creates a vacuum in the nozzle and pulls residual gas out of the line. Use only oil-free site compressors at 8–16 bar and at least 1.6 m³/min. Open a vent at the far end of the line. When the primary flame goes out: close the air, measure the gas concentration — only shut down below 50% LEL.

Oberes Steigrohr DN 50 mit optischer Flammenüberwachung

Optical flame monitoring

Optional for both units — optical monitoring reliably checks the flame, even with hard-to-see gases such as hydrogen.

Optical flame monitoring = a sensor detects via light/UV whether the flame is burning and reports any flame-out immediately.

On site

Shown: the display of the optical flame monitor. Press the central main switch — red LED = battery OK, no flame detected (including methane and hydrogen), green LED = flame burning. The LiFePO4 battery lasts about 120 hours of continuous operation; recharge after 20 days of non-use at the latest.


Ready in 2 minutes

Quick setup — the unit is ready to operate in about two minutes. The necessary tools are included in the case, ideal for changing sites.

Everything from one source

Advice, maintenance and service straight from AB Industrie — short routes, easy to reach and dependable.

Briefings & training

We brief your team and train the safe handling of flaring technology — hands-on and on-site on request.

Technical data

DN 25 or DN 50 — compared directly

Configurator

Which version do I need?

Five answers are enough. You get the matching version with its part number and the accessories to go with it — and can request the whole package.

What pressure is on the line?
How much residual gas, roughly?
Which gas are you flaring?
What is the unit standing on?

Ground spikes for natural soil are included with every flare. They only fail on hard or uneven ground — then ballast plates are added.

What else should be included?

A pre-selection, not a binding specification. What counts is the flow pressure at the unit — if in doubt, give us a call.

Flow rates (≈ 700 / 2,000 m³/h) apply at 5 bar flow pressure at the flaring unit and are DBI-tested in this range (DBI tests up to 5 bar). The DN 50 operates up to 16 bar flow pressure — so significantly higher throughputs are possible.
FeatureGasfackel DN 25Gasfackel DN 50
Nominal sizeDN 25 (1")DN 50 (2")
Flow at 5 bar~700 m³/h~2.000 m³/h
Pressure range5 mbar – 5 bar5 mbar – 16 bar
Flashback arrestorup to 1.5 bar H₂ · 5 bar methane/biogas/propanenot required by design
Non-return safetybis 5 barbis 16 bar
Safety valveGRS25 (IBEDA) · DVGWGRV50 (IBEDA) · DVGW
IgnitionPiezo propane igniterPiezo propane igniter
Flame monitoringoptional opticaloptional optical
Gas typesNatural gas · biogas · propane · town gas · H₂Natural gas · biogas · propane · town gas · H₂
Connection hose · standardISO 3821 (EN 559)EN 1762:2018 · CE
Temperature range−20 °C … +70 °C−20 °C … +70 °C
MaterialStainless 1.4301, bead-blastedStainless 1.4301, bead-blasted
Total height2.140 / 2.230 mm2.145 / 2.240 mm
Weight (unit + trolley)15 + 15 kg38 + 27 kg
Transport trolley (L × W × H)1.190 × 492 × 222 mm1.458 × 469 × 285 mm
Pre-filter0.1 mm · on the main pipe0.1 mm · in the hose connection
Typical useDistribution grids, house connections, small tanksTransmission / high-pressure lines, pipelines

Rule of thumb: For residual-gas volumes up to roughly 700 m³/h (at 5 bar) the DN 25 is sufficient. If you regularly flare larger flows or work at high pressure, the DN 50 is the safe choice — and it also covers the DN 25 range for mixed use.

When does a gas flare need a flashback arrestor? It depends on whether the flare tube is open at the top. On the DN 50 it always is: no back pressure can build up that would let a flame travel back into the line. A flashback arrestor is therefore not required by design – the unit carries the IBEDA GRV50 gas non-return valve, and in the 5 bar version the GRS50 safety fitting to DIN EN ISO 5175-2. Before every job you have to check that the flare tube is clear anyway. There is no silencer for the DN 50. The DN 25 comes with a screw-in silencer in its case. Once it is fitted, the system is no longer open at the top – and then a flashback arrestor is mandatory. Without the silencer the same applies as for the DN 50.

Transport and carrying The trolley rolls. If it has to be carried, the manufacturer specifies the end handles and two people — otherwise the permissible load is exceeded. If only one person is available, the trolley and the riser unit can be carried separately. On the DN 25 that is 15 kg for the unit and 15 kg for the trolley, on the DN 50 38 kg and 27 kg.

Versions and part numbers

PREMIUM means stainless steel on both sizes. PRO stands for the venturi nozzle, PLUS for flame monitoring. Only the DN 25 also comes as ECO — there the IBEDA safety fitting is brass instead of stainless steel.

All DN 25 versions are supplied with a trolley.
Gasfackel DN 25EquipmentPart number
ECOIBEDA safety fitting in brass960800-001
PREMIUMStainless steel, without venturi nozzle960800-002
PREMIUM PROStainless steel, with VENKRO 25 venturi nozzle960800-003
PREMIUM PRO PLUSStainless steel, with VENKRO 25 venturi nozzle and flame monitoring960800-004
Gasfackel DN 50Equipment 5 barGRS50 safety fitting 16 barGRV50 gas non-return valve
PREMIUMStainless steel, without venturi nozzle960850-004960850-008
PREMIUM PLUSStainless steel, with flame monitoring960850-003960850-007
PREMIUM PROStainless steel, with VENKRO 50 venturi nozzle960850-002960850-006
PREMIUM PRO PLUSStainless steel, with VENKRO 50 venturi nozzle and flame monitoring960850-001960850-005
AccessoriesDescriptionPart number
Degassing hose DN 19GWPB 19 × 4.5 mm · propane, natural gas and biogas · PN 20 · ISO 3821 · various lengths960810
Degassing hose DN 5050 × 8.5 mm · propane, natural gas and biogas · various lengths960860
Volume metering caseup to 16 bar · natural gas and biogas, propane, hydrogen and other gases960840

System components in detail

Volume metering case
Principle
Kármán vortex street · density-independent
Range
2,5–250 m³/h · up to 16 bar
Accuracy
± 1,5 % of reading
Signal / sensors
4–20 mA · PT100 (3-L) · barometric sensor
Connectivity
Wi-Fi hotspot · SCADA (LAN/WLAN) · PDF
Housing
Trolley PP · IP 44 · 560×290×460 mm
Weight
ca. 42,5 kg
Pressure-reducing stationNEW
Medium
Methane, hydrogen
Inlet pressure
40–100 barg
Outlet pressure
10–25 barg
Flow
methane 1,800 · H₂ 4,800 Nm³/h
Size / Kvs
DN 40 · Kvs 2,5 m³/h
Safety
ATEX fittings · 0.5 mm pre-filter · anti-tip
Build
Stainless · 4 wheels · crane-lift eyes
Gasfackel auf einer Betonfläche, im Hintergrund ein Anhänger mit Anlagentechnik.
Gasfackel auf einer Betonfläche, daneben die Propanflasche für die Zündflamme.
Mitarbeiter mit Helm und Warnkleidung neben Feuerlöscher und Transportkoffer, die Flamme im bewölkten Himmel.

Performance classes

What your line pressure decides about the choice of unit

The decisive question is not which flare is bigger. It is: what line pressure can you connect to directly — without reducing first?

Performance classMaximum pressureDirect connection up towithout pressure reduction
Small flare for service connectionsaround 1 bararound 1 bar
Mobile low-pressure flarearound 1 bararound 1 bar
Mobile medium-pressure flarearound 2 bararound 2 bar
Gasfackel DN 255 bar5 bar
Gasfackel DN 5016 bar16 bar
Gasfackel DN 50with pressure reduction station100 barg16 bar

About these figures: The figures for the market classes summarise publicly available manufacturer data and deliberately name no individual competitors. Throughput values from different manufacturers refer partly to normal cubic metres, partly to operating cubic metres — a direct numerical comparison is therefore only possible to a limited extent. What is unambiguously comparable is the permissible pressure.

What that means on site

You are standing at a line with 4 bar. With a flare rated for 1 or 2 bar you also need pressure reduction: another unit that has to be transported, set up, connected and included in the risk assessment. With the DN 50 you connect directly.

The surcharge for the 16 bar version over the 5 bar version is €175 — on a unit price from €11,119 net that is 1.6 %. Anyone who works on a line above 5 bar even once a year has recovered it.

And if the pressure is higher still?

For transmission lines and pipelines at 40 to 100 barg there is the mobile pressure reduction station: it brings the pressure down to 10 to 25 barg, with ATEX-certified fittings, for methane and hydrogen. The same DN 50 then covers the high-pressure range too, instead of requiring a second flare system.

Not sure what pressure actually reaches the unit in your case? That is exactly what the consultation is for — static pressure and flow pressure are two different things.

Accessories

Accessories for set-up, connection and safety distance

A flare alone is often not enough for a compliant operation. The volume metering case is listed above as a system component — here is the supplementary accessory range, matched to DN 25 and DN 50.

Diffusor-Verlängerung DN 50 für mehr Sicherheitsabstand
Diffuser extension DN 50

Raises the flame outlet by 1,800 mm for greater safety distance and visibility. Stainless V2A, with three eyelets for guy ropes. Use only from 1 bar line pressure — at lower pressure the flame burns incompletely inside the tube.

On requestView product
Beschwerungsplatten-Set zur Sicherung des Stativs
Ballast plates (set of 3)

Secure the stand against slipping and tipping — especially in wind and on hard or uneven ground. Quick to place, no tools.

On requestView product
Entgasungsschlauch DN 19 für Propan, Erdgas und Biogas
Degassing hose DN 19

GWPB DN 19 × 4.5 mm for propane, natural gas and biogas, PN 20, ISO 3821, any length — matches the DN 25. Not approved for hydrogen.

On requestView product
Entgasungsschlauch DN 50 für Propan, Erdgas und Biogas
Degassing hose DN 50

DN 50 × 8.5 mm for propane, natural gas and biogas — EN 1762:2018 · CE, matches the DN 50, fittings at both ends. Not approved for hydrogen.

On requestView product
Transportkoffer (Trolley) aus Edelstahl für das Abfackelgerät
Transport trolley

Protects unit and accessories in transit and storage — separately for DN 25 and DN 50, stainless 1.4301.

On requestView product
Lieferumfang: Erdspieße, Anschluss-Adapter und Manometer
Included in delivery

Ground stakes, connection adapters, pressure gauge and transport case are part of the unit — all in stainless steel 1.4301. Not included: degassing hose and the propane cylinder for the pilot flame. We supply the matching hose; for hydrogen we refer you to Mordhorst.

included

Buy, hire or have us flare

Three ways to get rid of your residual gas

You do not necessarily have to buy a unit. Which route suits you depends on how often you flare and whether you have your own trained staff.

Buy

  • Suitsregular demand, several crews, short-notice availability
  • You needyour own trained staff
  • Documentationwith the volume measuring case
View units and prices

Hire

  • Suitssingle project, incident, trial run before procurement
  • You needyour own staff, briefing bookable
  • Documentationvolume measuring case hireable separately
View hire terms

Have us flare

  • Suitsonce or twice a year, no own staff
  • You neednothing but clear space and a contact person
  • Documentationproduced by us on request
View flaring service

Hire

Hiring instead of buying a gas flare — when it pays off

For a single construction project, an incident or a trial run before procurement you do not need to buy a unit. Both sizes are available for hire — fully equipped.

FeatureHirePurchase
Suitssingle project, incident, trial run before procurementregular network operation, several crews
Minimum period1 day · dispatch to return
Billingdaily, weekly or monthly rateone-off
Depositnormally none
Creditcreditable against a later purchase by arrangement

What you get when hiring

  • Gasfackel DN 25ready for use in the transport case, with VENKRO 25 venturi nozzle
  • Gasfackel DN 50ready for use in the transport case, with VENKRO 50 venturi nozzle and optical flame monitoring
  • Degassing hoseson request, matching the size
  • Volume measuring casehireable separately if you have to document the flared quantity

Our hire units are consistently fully equipped — you are not renting the stripped-down version.

Delivery and briefing

Delivery by forwarder, delivery by us or collection in Leipzig — your choice. A briefing at the unit is available on site for a surcharge, or online via Teams or Meet. By phone works too, but it is the more awkward route: when flaring, it helps if we are both looking at the same unit.

Incident? If a hire unit is in stock, you can collect it in Leipzig within one hour. Call instead of ordering — on the phone it takes two minutes to establish what is available.

Tell us the period, the application and the line pressure. We will quote daily, weekly and monthly rates on request.

Aufbauplatz auf Pflaster: geöffneter Transportkoffer und aufgerollter Schlauch, dahinter die brennende Fackel auf der Wiese.
Nahaufnahme des Stativfußes mit Erdspieß im Gras, daneben der angeschlossene Entgasungsschlauch.
Gasfackel vor einem Betriebsgebäude, die Flamme reicht über das Dach.

Flaring service

We do the flaring for you — throughout Germany

You do not have to buy a unit, nor hire one. If you need to get rid of residual gas once or twice a year, we come to you with the flare and carry out the operation.

What we have already flared

Natural gas boreholes Pipelines ahead of overhaul Propane tanks emptied Hydrogen vessels at filling stations emptied Biogas plants degassed

How the job runs

The scope follows your needs: setting up and running the flare only, or additionally recording the quantity with the volume measuring case including the log for your documentation. On site you will find the owner himself or a colleague. We operate throughout Germany; at short notice too if unit and staff are available. Billing by arrangement — scope and effort depend on the job.

What you provide

We work with an open flame and corresponding thermal radiation. For the job to work, we need the following from you:

  • Clear space all around the set-up point — the area depends on local conditions, we clarify that beforehand
  • An oil-free compressor if the line is to be evacuated with the venturi nozzle (8–16 bar, at least 1.6 m³/min)
  • A contact person on site
  • Notification of the fire brigade where required

We bring the propane cylinder for the pilot flame ourselves.

Only you can judge which approvals and permits your site requires — that depends on your plant, your operator and the local authority. We tell you what we need technically; the operational clearance rests with you.

Applications

Three situations in which residual gas has to go

01

Degassing before repair

Before any work on a line, the residual gas must go. The flare burns it in a controlled way outside the work area.

02

Purging before commissioning

During filling, gas displaces the air. The gas-air mixture passes through the flare and is burned off cleanly.

03

Documentation per EU regulation

Flow rate and volume must be captured and archived — handled by the volume metering case in parallel.

Grid operators Municipal utilities Oil · Gas · Chemical Biogas plants Hydrogen (H₂) Gas storage Pipeline construction Refineries Chemical parks Plant engineering

Procedure

How a flaring operation works

Using the DN 50 gas flare as the example — from setting up to the packed case. The DN 25 works the same way, just one size smaller.

Setting up

  1. Choose the locationLevel ground, clear overhead, no vegetation, no ignition sources, two escape routes.
  2. Set up the flareOpen the trolley, raise the riser, fold out the three legs until they lock.
  3. Earth and secureDrive in the earth spikes with a non-sparking hammer, connect the earthing cable. On asphalt: weighting plates.
  4. Fit the upper riserFlat gasket centred, tighten by hand, then a further 30–45° with the hook wrenches.
  5. Connect upDegassing hose via 2″ or 2½″ adapter, piezo burner, propane cylinder, pressure gauge.

Flaring

  1. Check for leaksPropane side first, then the gas side — with a gas detector or by soaping the joints.
  2. Match the unit to the pressureGRS 50 up to 5 bar, GRV 50 up to 16 bar flow pressure. If the pressure does not match, it is reduced.
  3. Light the pilot flameRegulator to 1.0 bar, ignite, lock, back to 0.5 bar. Always before the main shut-off valve.
  4. Open the gas supplySlowly but fully. Never throttle ball valves. The flame must burn upwards.
  5. Flare off and measurePressure drops, flame shrinks. Measure the concentration at the test connection, draw down with the VENKRO 50.

Dismantling

  1. Shut downClose the gas line first, then the propane cylinder. Burner valve shut, then open all valves.
  2. Take apartPressure gauge, burner, hose, upper riser. Refit the protective caps, secure the flat gasket.
  3. Pack awayOnly once fully cooled. Pull the earth spikes, fold the legs, into the trolley.

This overview does not replace the operating manual. What is binding is the unit's operating manual and the rules for working on gas-carrying systems, such as DGUV Information 203-090. The manual comes with every unit; we will send it to you in advance on request. Would you rather hand the job over? We can flare for you.

Gasfackel auf einer Wiese neben einer Rohrleitungsanlage.
Gasfackel an einer offenen Baugrube, daneben ein Bagger.
Zwei Gasfackeln nebeneinander auf einer Asphaltfläche, im Hintergrund ein Feuerwehrfahrzeug.

Knowledge & practice

Guides on gas flaring

Questions that come up on the phone again and again — answered in more depth than a FAQ allows.

What blinds measuring instruments without anyone noticing

Silicone does nothing to the flare. It does plenty to the Ex and methane detectors on the same job — and nobody notices.

Siloxane vapours burn to silicon dioxide on the hot catalyst and settle as a glassy layer on the active surface. The sensor does not die, it goes deaf. That is exactly what makes it dangerous: a failure is noticed, a reading that is too low is not.

Sensor typeWhat happens
Pellistor — catalytic bead, Ex and CH₄ measurementThe most critical case. SiO₂ coats the active surface, the reading drops too low or to zero. Irreversible — the sensor has to be replaced.
Zirconia O₂ — residual oxygen, 600–700 °CSame mechanism, because it also works hot. SiO₂ clogs the porous electrode: drift and sluggish response.
Electrochemical cell — O₂, CO, H₂SLess prone to actual poisoning. But an aerosol film on the sintered filter and diffusion membrane lengthens the response time and damps the reading.
NDIR / infraredImmune to poisoning. But a silicone film on window and mirror reduces transmission — usually still recoverable by cleaning.

Spray mist from several metres away, or vapours from freshly treated parts in the same room, is enough.

In practice: silicone spray does not belong in the same tool case or the same cab as the instrument. The same goes for silicone-based sealing greases, mould release agents, leak detection sprays and some hand care products. For seals and PE push-fit connections use silicone-free lubricants — soap- or PTFE-based. That is the better choice anyway, because silicone residues later cause wetting defects in coating and problems in welding.

How much residual gas is in the line?

Two figures are enough for the quantity: line volume and pressure. For the duration there is no such formula.

The gas quantity under standard conditions follows from the geometric volume of the section and the absolute pressure:

Standard volume ≈ length × cross-section × absolute pressure

The absolute pressure is the operating pressure plus roughly 1 bar of atmospheric pressure. The cross-section is π/4 × diameter squared.

Sectiongeometricstandard conditions
Distribution main DN 200, 500 m, 4 bar15,7 m³~79 m³
Transmission line DN 500, 5 km, 16 bar982 m³~16.700 m³

For the duration this is a rough orientation at best. At 5 bar flow pressure the DN 50 handles around 2,000 m³/h — at 5 bar. As the pressure falls, so does the flow; towards the end hardly anything comes through.

And then the second part only begins: the venturi nozzle works only once the line is depressurised. How long it takes for the reading to drop below half the lower explosive limit depends on the condition of the line — incrustations and deposits keep releasing gas for a long time. Nobody can predict that precisely.

And the calculation applies to the section between the shut-off valves. Which section that is, only the operator knows.

Pump over first, then flare

We sell flares — and still advise against burning gas that can be pumped over.

Gas is a commodity. What stands in the line has been paid for by the operator; letting it burn costs that money a second time. Before an inspection a section is therefore usually pumped over — into an adjacent section, into storage, back into the grid.

That does not empty the line completely. Whatever remains after pumping over still has to come out before anyone opens the line. That is where flaring begins — not with a full line.

And there are cases where pumping over is not possible. Whether that applies is decided by the operator case by case. It cannot be judged from outside.

  • Flaring releases the overpressure. As long as there is pressure on the line, the gas flows by itself.
  • Extraction removes what no longer comes out on its own once the pressure is gone. The venturi nozzle creates a vacuum; extraction continues until the measured concentration is below half the lower explosive limit.

Without the second stage an ignitable mixture stays in the section. With it, the section can be cut.

When is flaring permitted at all?

Article 15 prohibits routine flaring — and puts rerouting first.

What the equipment has to be capable of is set out in Article 17 — you will find that further up this page. Article 15 governs something else: whether flaring is allowed at all.

“Venting shall be prohibited, except in the circumstances provided for in this Article. Routine flaring shall be prohibited.”Article 15(1)

Both are permitted only in an emergency, during a malfunction — or where they are unavoidable and strictly necessary. The Regulation lists specific situations for this. Two of them bear directly on mobile flaring:

  • paragraph 3(e) — during repair, maintenance, testing procedures and decommissioning, including blowdown and depressurisation.
  • paragraph 3(k) — when blowing down or purging a line for the purpose of repair, “but only where the gas cannot be contained or rerouted into an unaffected part of the line”.

The proviso in point (k) is exactly the rule from the topic above — only as legal text. Rerouting comes before flaring.

“In addition to the conditions set out in paragraphs 2 and 3, flaring shall only be allowed where either re-injection, utilisation on-site, storage for later use or dispatch of the methane to a market are not feasible for reasons other than economic considerations.”Article 15(6)

The decisive words in that sentence are “other than economic considerations”: the fact that rerouting would cost more is expressly not accepted as a justification.

And venting instead of flaring?

Conversely, flaring takes precedence over venting. Under paragraph 4, venting is only allowed where flaring is not technically feasible — because the flame cannot be ignited or sustained, because it would endanger safety, or because it would have worse environmental effects in terms of emissions. That justification has to be evidenced to the competent authority.

Reporting duties under Article 16

  • Events caused by an emergency or malfunction: report without delay, at the latest within 48 hours of their start.
  • Events lasting eight hours or more in total within 24 hours: likewise.
  • Controlled flaring during a shutdown: in the annual report.

Annex III lists the information to be provided. For the quantity you need a measurement — that is what the volume measuring case is for.

Who this applies to

The Regulation applies to the energy sector: production and processing of oil and fossil gas, wells, transmission and distribution of natural gas, underground storage, LNG facilities and coal mines (Article 1(2)). Biogas plants and industrial end users do not fall under it — different rules apply there.

This information reproduces the text of the Regulation and does not constitute legal advice.

What has to be settled before the job

Most delays on site have nothing to do with the equipment.

Details of the section

  • Operating pressure and medium
  • Volume, or length and diameter
  • which shut-off valves bound the section

Without these details neither the size nor the safety device can be determined.

Requirements for the site

  • level and firm, completely clear overhead
  • clear working space all round — we work with an open flame and the heat radiation that comes with it
  • no vegetation, no ignition sources, two escape routes

To be provided by you

  • Personal protective equipment, warning signs, gas detector
  • when the venturi nozzle is used, a site compressor for oil-free compressed air, at least 8 bar and 1.6 m³/min

We bring the propane cylinder ourselves when we carry out the job.

What only you can decide

Whether the fire brigade has to be informed, whether permits are required, how the risk assessment turns out — that depends on your local conditions and internal rules. DGUV Information 203-090 is the guidance document for this. We can advise, but we cannot decide it for you.

In more depth on the AB Industrie blog

Frequently asked questions

Gas flares, flaring & the EU Methane Regulation — briefly explained

What is a gas flare or flaring unit?
A gas flare (flaring unit) burns residual gas from pipelines or tanks in a controlled way outside the working area. This avoids methane emissions before a line is worked on or newly commissioned.
DN 25 or DN 50 — which gas flare do I need?
The DN 25 flares around 700 m³/h at 5 bar flow pressure and suits distribution networks and house connections. The DN 50 handles around 2,000 m³/h; we supply it as standard in the 16 bar version — so far we have sold that version exclusively. It is the choice for transmission and high-pressure lines as well as pipeline construction. For mixed duties the DN 50 also covers the DN 25 range. Anyone working on lines above 5 bar saves the upstream pressure reduction and its set-up with the 16 bar version.
Which gas types can be flared?
Natural gas, biogas, propane, town gas and hydrogen (H₂-ready). Both sizes are multi-gas capable. With hydrogen the optical flame monitoring is particularly important because the H₂ flame is barely visible to the naked eye — irrespective of the gas type, Article 17(4) of the EU Methane Regulation requires a flame monitor anyway when a continuous pilot burner is used. In January 2025 DBI tested the DN 25 with pure hydrogen and certified complete burnout up to 0.4 bar and 360 m³/h.
What does the EU Methane Regulation 2024/1787 require for flaring?
Two things. First, the unit itself must meet Article 17: at least 99 % destruction and removal efficiency plus an auto-igniter or continuous pilot burner. The deadline for all units expired on 5 February 2026. Second, Article 15 restricts flaring as such: routine flaring is prohibited, while it remains expressly permitted for repair, maintenance and decommissioning as well as for purging during commissioning. Flared quantities must be reported under Article 16.
Which regulations apply to mobile flaring in the gas network?
The relevant framework is EU Methane Regulation 2024/1787 with three applicable articles: Article 15 restricts flaring as such, Article 16 governs the reporting duty, Article 17 sets the requirements for the unit. In addition there are the DVGW codes G 404 (technical reduction of methane and hydrogen emissions) and G 424 (guideline on reducing methane emissions) as well as TA Luft. Our gas flares are tested by DBI Freiberg to the EU Methane Regulation, VDI 2105 (10/22) and TA-Luft (08/2021); quantity recording is handled by the volume measuring case.
How is the flared gas volume documented?
The volume metering case measures density-independently using the Kármán principle in the range 2.5–250 m³/h up to 16 bar with ± 1.5 % accuracy and automatically generates PDF logs — available via Wi-Fi or SCADA.
Are the gas flares certified?
Yes. DBI — Gastechnologisches Institut gGmbH Freiberg tested both sizes to EU Methane Regulation 2024/1787, VDI 2105 (10/22) and TA-Luft (08/2021) (report no. 81-8108-2024). Both carry the DBI test mark. The GRS25 and GRV50 safety fittings (IBEDA) are DVGW-certified. EN 1762:2018 · CE and ISO 3821 (EN 559) apply to the connecting hoses, not to the unit itself.
Do you offer maintenance, service and spare parts?
Yes — maintenance, service and spare parts come directly from us. In our workshop in Leipzig (Plautstraße 80, 04179 Leipzig) we test, service and repair the units ourselves, without a detour via the manufacturer, and keep common spare parts in stock. This includes the annual inspection of the IBEDA safety fittings for tightness and safety against gas return required by the manufacturer's data — for the GRV50 in accordance with TRBS 1201, Table 2. We are an official sales and service partner of KROHSE GmbH for Germany — having the annual service done by us keeps warranty and liability in force.
How quickly is the gas flare ready for use?
In about two minutes. The necessary tools are included in the transport case — ideal for changing sites.
What does a mobile gas flare cost?
The DN 25 gas flare starts at €5,499 net, the DN 50 at €11,294 net — depending on the version. The volume measuring case for quantity documentation costs €10,990 net. All prices are net, plus 19 % VAT. Binding prices for all versions are in our shop.
Can I also hire a gas flare?
Yes, both sizes. The minimum hire period is one day. It runs from dispatch until the day the unit arrives back with us — so the shipping time in both directions counts. Billing is at a daily, weekly or monthly rate. We normally do not require a deposit, and by arrangement we credit the hire cost against a later purchase. The hire units are fully equipped: the DN 25 with the VENKRO 25 venturi nozzle, the DN 50 with the VENKRO 50 and additionally optical flame monitoring.
How long is the delivery time?
That depends on the version and the quantity. We configure every unit to your application — version, pressure rating, venturi nozzle, flame monitoring and matching hose. As a rule that goes quickly, but our stock is not unlimited: larger quantities or special configurations take longer. We give you a binding date with the quotation. Hire units are available at short notice provided they are not out on another job — in that case call us rather than ordering.
Can you also carry out the flaring for us?
Yes, throughout Germany. We come to you with the flare and carry out the flaring operation — including quantity recording and a log on request. On site you will find the owner himself or a colleague. Among other things we have flared natural gas boreholes, pipelines ahead of overhaul, propane tanks, hydrogen vessels at filling stations and biogas plants.
Do I need flame monitoring?
Article 17(4) of the EU Methane Regulation requires: where auto-igniters or continuous pilot burners are used, operators must employ flame monitors for continuous monitoring of the main or pilot flame. Our units work with a continuous pilot burner. The optical flame monitoring performs this task and is included in the PREMIUM PRO PLUS (DN 25) and PREMIUM-PRO+ (DN 50) versions. We recommend it — particularly for hydrogen, whose flame is barely visible. Whether it is required for your application is for you or your consulting engineer to assess.
What safety distance must I maintain?
We deliberately do not specify one — the risk assessment is the operator's responsibility and we do not know your site. Two points to plan for: at low pressures wind plays a major role and the flame drifts sideways. At high pressures considerable thermal radiation develops upwards and to the side. The DN 50 diffuser extension raises the flame outlet by 1,800 mm and noticeably reduces radiant heat at ground level. Describe your situation to us — we will tell you what we watched out for in comparable cases.
What compressed air do I need for the venturi nozzle?
An oil-free site compressor with 8–16 bar and at least 1.6 m³/min. Any oil carry-over must be avoided. A vent must be opened at the opposite end of the line. If the primary flame goes out in the process: close the compressed air, measure the gas concentration — only shut down below 50 % LEL.
Why don't you state explosion groups?
Because they are not the appropriate designation for our design. The IBEDA GRS and GRV safety fittings are built to DIN EN ISO 5175-2. That standard classifies by gas type and working pressure — which is why you find figures such as “up to 5 bar methane” rather than “IIA/IIB/IIC”. Explosion groups come from the standards for components with an integrated flame arrester. We are happy to clarify with you which design suits your application.
What is included in the scope of delivery — and what is not?
Included are ground stakes, connection adapters, a pressure gauge and the transport case — all in stainless steel 1.4301. Not included are the degassing hose and the propane cylinder for the pilot flame. We supply the matching hose; for hydrogen we do not carry hoses and refer you to Mordhorst. All units are supplied exclusively with a transport case — that way every part has its place on the way to the site.
Do the safety fittings have to be tested regularly?
Yes. The IBEDA data sheets require the safety devices to be tested at least once a year by a trained and authorised person for gas tightness and safety against gas return — for the GRV50 expressly in accordance with TRBS 1201, Table 2. The fittings must not be opened; the dust filter may be cleaned or replaced. We carry out this inspection in our workshop in Leipzig.
How do I get a quote for a gas flare?
Via the contact form or by phone on +49 176 10216596. Four details help: application, estimated residual gas quantity, line pressure and gas type — you can select them directly in the form. We recommend the right unit including measuring equipment and accessories, and usually reply within one working day.
Wärmebildkamera vor der Flamme: Anzeige FIRE bei 449 °C.
Gasfackel bei Regen auf dem Gelände einer Station, daneben ein Feuerlöscher.
Gasfackel am Rand eines Waldwegs, mit Feuerlöscher und Warnschild abgesichert.

Why AB Industrie

Advice, servicing and spare parts from Leipzig

Many supply a flare. We supply the complete, verifiable flaring process — coordinated equipment from a single source, backed by service and spare parts.

Complete solution from one source

Flare, volume metering case, pressure reduction station and accessories — coordinated with each other instead of individual parts from different suppliers. One contact for the whole process.

Empty down to the ppm range

The Venturi nozzle actively draws the residual gas out of the line — well below 50 % LEL, down to the ppm range. Separate nitrogen purging can therefore be omitted.

Rent or buy

Rent for a single project or buy permanently — you decide flexibly depending on how often you use it. Including briefing and delivery on request.

High pressure & high throughput

Up to 16 bar inlet pressure and around 2,000 m³/h (DN 50) — with the pressure reduction station even pipeline pressures up to 100 bar. Significantly more than common low-pressure flares.

Service & spare parts on site

Maintenance, repair and common spare parts directly from our workshop in Leipzig — without a detour via the manufacturer, quickly reachable and with briefing on request.

Verifiable EU documentation

The volume metering case automatically logs flow rate and volume as a PDF — audit-proof for authorities, QA and audits under the EU Methane Regulation 2024/1787.

Annual inspection and servicing — in Leipzig, not on site

The IBEDA safety fittings must be tested at least once a year for tightness and safety against gas return — for the GRV50 in accordance with TRBS 1201, Table 2. This cannot be done on site: the unit is completely dismantled for it. Test and inspection equipment as well as the special jig for dismantling and assembly are located exclusively in our workshop in Plautstraße. We have already serviced and tested dozens of units there.

What happens during servicing

  • The unit and transport case are cleaned, the burner mount checked for damage
  • The safety fitting is released, the basket filter removed, threads and fitting cleaned
  • Testing of the IBEDA fitting for gas non-return function in accordance with TRBS 1201
  • A new basket filter (stainless steel 1.4305, 100 µm) and new seals are fitted
  • Folding feet checked at 10 Nm, ball of the main shut-off valve and pressure gauge coupling lubricated
  • O-rings on degassing hoses and adapters are replaced, all threaded connections checked
  • Pressure gauges checked for accuracy — permissible deviation no more than 100 mbar from full scale
  • Piezo burner, propane hose and pressure regulator checked, degassing hoses for cracks, porosity and kinks
  • Finally a service label is applied to the unit

Tightness test with nitrogen

Test stepDN 25DN 50
up to the main shut-off valve8 bar24 bar
complete unit6 bar17 bar

The test is documented. You receive the inspection report with the service — for your files, quality management and evidence towards the authorities.

And before every use? Article 17(3) of the EU Methane Regulation requires an inspection before every use for irregularly used flares. We brief your team on what to look out for.

What you do yourself — maintenance level L1

The manufacturer distinguishes two levels. L1 you do yourself, right after the job. L2 is the annual service described above — the unit is completely dismantled for it.

  • After every job: let the unit cool down and clean it with Ballistol — no aggressive agents, they attack the corrosion protection and the seals
  • After every job: check the O-rings of the degassing hoses
  • After every job: check the piezo burner set for cracks in the hose and impact damage to burner and pressure regulator
  • After every job with the venturi nozzle: check seal, shut-off fittings and hose at the compressed-air connection, grease the safety claw coupling with Ballistol
  • Every third job: check the pressure gauge and its coupling for clean, undamaged connections and grease them
  • Every third job or sooner: take out the pre-filter screen, clean it with brake cleaner and blow it out — or replace it
  • After a job in wet conditions: dry everything and store it in a ventilated room

Degassing hose and propane hose have a service life of eight years. Temperature, UV light, contact with media and heavy mechanical stress shorten it — which is why the visual check belongs in the L1 routine.

Silicone does not harm the flare — it harms the instruments: The unit itself does not care about silicone. What is at risk are the Ex and methane detectors running on the same job: siloxane vapours burn to silicon dioxide on the pellistor and settle as a glassy layer on the active surface. The sensor does not die, it just goes deaf — the instrument keeps running and reads low or nothing at all. Spray mist from several metres away is enough. So silicone spray does not belong in the same tool case or the same cab as the instrument. More on this in the guide

Important for your warranty: The annual service is classified by the manufacturer as level L2 and may only be carried out by KROHSE GmbH or one of its service partners — otherwise warranty and liability claims lapse immediately. We are an official sales and service partner of KROHSE GmbH for Germany; with us both remain in force. KROHSE partner list

About us

From the trench, not from the catalogue

Frank Abraham founded AB Industrie Service in Leipzig in 2010 — after years of advising pipeline crews on site, in the trench, tool in hand. Nothing enters our range that we would not work with ourselves. For flaring equipment that is KROHSE: we are the official sales and service partner for Germany, advise before the sale, supply the right device with its accessories and service it later in our own workshop.

2010Founded in Leipzig
D · A · CHMain markets — delivery throughout the EU
Own workshopServicing, testing and repair in house
Manufacturer of the flaring units KROHSE GmbH — Hersteller der Abfackelgeräte
Abfackeltechnik von AB Industrie Service im Einsatz
Mobile Gasfackel von AB Industrie Service im Feldeinsatz
Abfackelgerät im Netz- und Pipelinebau
Gasfackel beim kontrollierten Abfackeln von Restgas
Mobile Abfackeltechnik aus Edelstahl im Einsatz
Gasfackel DN 50 im Feldeinsatz
Abfackelgerät von AB Industrie Service vor Ort
Mobile Gasfackel beim Entgasen einer Leitung
Abfackeltechnik im Einsatz bei Netzbetreibern

References

In service with operators and utilities

OGE — Open Grid Europe
SachsenEnergie
RheinNetz
Schleswig-Holstein Netz AG
Harbour Energy

What we have already flared

  • Natural gas boreholes
  • Pipelines ahead of overhaul
  • Propane tanks emptied
  • Hydrogen vessels at filling stations emptied
  • Biogas plants degassed

Our own jobs — carried out with our units, partly on assignment, partly as a service.

Where else residual gas occurs

Wherever gas is carried or stored, sooner or later the question arises: where does it go? During an overhaul, a repair, a conversion or a decommissioning. This list describes possible applications — not jobs we have carried out.

Distribution network and service connections Decommissioning and removal of connections and distribution lines · refurbishment and relocation · the L-to-H gas conversion running until 2030 · purging when commissioning new network sections
Transmission, storage, compression Transmission lines before pigging, overhaul or conversion · gas pressure regulating and metering stations · underground and cavern storage · compressor stations
Production and boreholes Natural gas boreholes and production tests · wells being decommissioned or plugged — Article 18 of the EU Methane Regulation obliges member states to inventory them
Biogas, sewage gas, landfill gas Biogas plants during maintenance on digesters or gas holders · sewage works when the CHP unit, boiler or the fixed emergency flare fails or is being serviced · landfills with gas collection
LPG Propane tanks before emptying, decommissioning or relocation · cylinder stores · tankers before repair
Hydrogen Hydrogen filling stations · electrolysers, test rigs and pilot plants · conversion and blending projects in the network
Industry and plant engineering Refineries and chemical parks during plant overhauls · industrial thermal process plants · CHP units and heating stations · gas-fired production plants before conversion
Dismantling and decommissioning CNG filling stations, many of which are currently being closed · complete plants before demolition · network sections being taken off the grid permanently

Your case not listed? It probably still fits. Tell us the residual gas quantity, line pressure and gas type — we will tell you whether it works and with which size.

Symbolbild persönliche Beratung bei AB Industrie Service

Personal advice

Three steps to the right unit

Small enough to listen. Large enough to deliver. No wading through catalogues, no guesswork: you describe the application, residual gas quantity, pressure and gas type — we recommend the right flaring unit including measuring equipment and deliver it. Across Europe.

  1. 1
    EnquireApplication, residual gas volume, pressure and gas type — briefly, by form or email.
  2. 2
    Recommendation & quoteWe recommend the right unit with metering technology and accessories — specific, with pricing.
  3. 3
    DeliveredAcross Europe, with on-site instruction on request.

ConfiguratorWhich version do I need? Five answers are enough — version, article number and accessories are then ready and go out with the enquiry.

Contact

Sound advice — from sale to service

Tell us your application and residual-gas volumes — we'll recommend the right unit and the metering you need.

Phone — you speak directly with the owner0176 10216596Mon–Fri from 8 a.m. · also via Signal and Threema
AB Industrie ServiceFrank Abraham
Adolph-Menzel-Straße 40
04157 Leipzig
Workshop · Service & spare partsPlautstraße 80
04179 Leipzig

Faster by phone: 0176 10216596 · Mon–Fri from 8 a.m.

A sketch or photo of the connection situation? Send it to info@ab-industrie.de or via Signal or Threema to +49 176 10216596 — one picture answers more questions than three emails.

We usually reply within one working day — with a specific recommendation, not a catalogue.

Workshop Leipzig · Plautstraße 80, 04179 Leipzig — Maintenance, service & spare partsGet directions
Call Enquire